23.24.040 Local Amendment Regarding Electric-readiness and Energy Performance of Single-Family Residential Buildings.
(a) Energy Code subsection 150.0(t) is amended to read as follows:
(t) Heat pump space heater ready. Systems using gas or propane furnace to serve individual dwelling units shall include the following:
1. A dedicated 240 volt branch circuit wiring shall be installed within 3 feet from the furnace and accessible to the furnace with no obstructions. The branch circuit conductors shall be rated at 30 amps minimum. The blank cover shall be identified as "240V ready." All electrical components shall be installed in accordance with the California Electrical Code.
2. The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a future heat pump space heater installation. The reserved space shall be permanently marked as "For Future 240V use."
3. A designated exterior location for a future heat pump compressor unit with either a drain or natural drainage for condensate.
(b) Energy Code subsection 150.1(b) is amended to read as follows:
(b) Performance Standards. A building complies with the performance standards if the energy consumption calculated for the proposed design building is no greater than the energy budget calculated for the standard design building using Commission-certified compliance software as specified by the Alternative Calculation Methods Approval Manual, as specified in sub-sections 1, 2 and 3 below.
1. Newly Constructed Buildings. The Energy Budget for newly constructed buildings is expressed in terms of the Energy Design Ratings, which are based on source energy and time-dependent valuation (TDV) energy. The Energy Design Rating 1 (EDR1) is based on source energy. The Energy Design Rating 2 (EDR2) is based on TDV energy and has two components, the Energy Efficiency Design Rating, and the Solar Electric Generation and Demand Flexibility Design Rating. The total Energy Design Rating shall account for both the Energy Efficiency Design Rating and the Solar Electric Generation and Demand Flexibility Design Rating. The proposed building shall separately comply with the Source Energy Design Rating, Energy Efficiency Design Rating and the Total Energy Design Rating. A building complies with the performance approach if the TDV energy budget calculated for the proposed design building is no greater than the TDV energy budget calculated for the Standard Design Building AND Source Energy compliance margin of at least 9, relative to the Source Energy Design Rating 1 calculated for the Standard Design building.
Exception 1 to Section 150.1(b)1. A community shared solar electric generation system, or other renewable electric generation system, and/or community shared battery storage system, which provides dedicated power, utility energy reduction credits, or payments for energy bill reductions, to the permitted building and is approved by the Energy Commission as specified in Title 24, Part 1, Section 10-115, may offset part or all of the solar electric generation system Energy Design Rating required to comply with the Standards, as calculated according to methods established by the Commission in the Residential ACM Reference Manual.
Exception 2 to Section 150.1(b)1. A newly constructed building with a conditioned floor area less than 1,500 square feet shall achieve a Source Energy compliance margin of 4 or greater, relative to the Source Energy Design Rating 1 calculated for the Standard Design building.
Exception 3 to Section 150.1(b)1. A newly constructed building with a conditioned floor area less than 625 square feet shall achieve a Source Energy compliance margin of 0 or greater, relative to the Source Energy Design Rating 1 calculated for the Standard Design building.
Exception 4 to Section 150.1(b)1. A newly constructed Accessory Dwelling Unit, as defined by San Mateo Municipal Code Section 27.04.165(a), shall achieve a Source Energy compliance margin of 0 or greater, relative to the Source Energy Design Rating 1 calculated for the Standard Design building.
(c) Energy Code subsections 150.1(b)2, 150.1(b)3, and 150.1(c) are adopted without amendments.